IRIS ultraviolet scanner for Ex area IRIS500 UV Ex - Data sheet - DownloadIRIS500 UV Ex - Data sheet - Download ATEX - INERIS 03ATEX0175X - Certificate downloadATEX - INERIS 03ATEX0175X - Certificate download

Description

The ultraviolet viewing head is recommended for gas and oil flames. It consist of a gas discharge type sensor with a spectral response only in the UV region, approximately 185 to 300 nanometers with a peak response at 200 nanometers. The highest UV intensity occurs near the flame root (first 30% of the flame) but this zone of higher UV intensity does not overlap the same zone of adiacent or opposing burner so that, with proper sighting, discrimination is predictable.


Characteristics

  • Degree of protection: IP66
  • Flame detector unit
  • Self checking by electronic switching
  • Shutter frequency: 1 every second
  • Waves spectrum detected: 340-3000nm
  • IR lens optical/trasmittance: 209-3600nm
  • Angle of view: 2.7 maximum
  • Connection to the burner: 1"NPTF
  • Purge air connection: 1/2" NPTF
  • Purge air flow required: approx 1,7cbm/h
  • Electrical connection: 3/4"NPTF
  • To be use with  IRIS500-MA flame amplifiers