Products

Flame Detector Systems - IRIS500 UNISCAN IP

IRIS 500 UNISCAN IP IRIS500 UNISCAN IP - Data sheet - DownloadIRIS500 UNISCAN IP - Data sheet - Download

Description

The IRIS uniscan IP is a fail safe flame monitor and amplifier, mounted completely into one enclosure. Its purpose is to monitor gas or oil flames in process heaters, or the smaller utility boilers. The operating voltage range is 18 to 27VDC, so that losses or fluctuations in the voltage have no effect within these parameters. The flame on output is a 24VDC signal. As well as gain and drop out time adjustments a high band pass filter with four positions is provided for better discrimination. A DIN rail mounting power supply module, to provide a 24VDC output from a 115/230VAC input is available if required. A commissioning module is also available. It is battery powered, and is capable of powering the UNISCAN on the boiler front for approx. one hour. This enables an evaluation on performance, without the need for separate power supplies and wiring.

Characteristics

  • Degree of protection: IP65
  • Flame monitor and amplifier
  • Fail safe 100%
  • Self checking by electronic switching
  • Waves spectrum detected: 750-1900nm
  • Supply voltage 24VDC
  • Output 1 normal open volt powered 24VDC contact for flame on (SPST)
  • Angle of view: 2.7 maximum
  • Electrical connection: amphenol plug on rear of enclosure
  • Flame drop out time selectable to 1 - 2 or 3 seconds
  • Flame signal amplifier required: IRIS500-SRM